14 UNT-SVX07B-EN
Dimensions and Weights
Table 1. Fan-coil component data
Unit Size 02 03 04 06 08 10 12
Coil Data
Face Area — ft
2
(cm
2
) 0.8 (743) 0.8 (743) 1.1 (1020) 1.6 (1490) 2.1 (1950) 3.2 (2970) 3.2 (2970)
LxDxH — in. (cm)
2-Row 15 x 1.7 x 8 15 x 1.7 x 8 20 x 1.7 x 8 29.5 x 1.7 x 8 38 x 1.7 x 8 57 x 1.7 x 8 57 x 1.7 x 8
(38 x 4 x 20) (38 x 4 x 20) (51 x 4 x 20) (75 x 4 x 20) (97 x 4 x 20) (145 x 4 x 20) (145 x 4 x 20)
3-Row 15 x 2.6 x 8 15 x 2.6 x 8 20 x 2.6 x 8 29.5 x 2.6 x 8 38 x 2.6 x 8 57 x 2.6 x 8 57 x 2.6 x 8
(38 x 7 x 20) (38 x 7 x 20) (51 x 7 x 20) (75 x 7 x 20) (97 x 7 x 20) (145 x 7 x 20) (145 x 7 x 20)
4-Row 15 x 3.5 x 8 15 x 3.5 x 8 20 x 3.5 x 8 29.5 x 3.5 x 8 38 x 3.5 x 8 57 x 3.5 x 8 57 x 3.5 x 8
(38 x 9 x 20) (38 x 9 x 20) (51 x 9 x 20) (75 x 9 x 20) (97 x 9 x 20) (145 x 9 x 20) (145 x 9 x 20)
Volume — gal (L)
1-Row (Heat) 0.06 (0.23) 0.06 (0.23) 0.08 (0.30) 0.11 (0.42) 0.14 (0.53) 0.21 (0.79) 0.21 (0.79)
2-Row 0.12 (0.45) 0.12 (0.45) 0.15 (0.57) 0.22 (0.83) 0.28 (1.06) 0.42 (1.59) 0.42 (1.59)
3-Row 0.18 (0.68) 0.18 (0.68) 0.23 (0.87) 0.33 (1.25) 0.42 (1.59) 0.62 (2.35) 0.62 (2.35)
4-Row 0.24 (0.91) 0.24 (0.91) 0.30 (1.14) 0.44 (1.67) 0.56 (2.12) 0.83 (3.14) 0.83 (3.14)
Fins/ft (cm)
2-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
3-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
4-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
Reheat Coil Data (1-Row), Standard or High-Capacity
(a)
(a) Standard and high-capacity reheat coils share the same component data except that standard capacity reheat coils have 48 fins/ft (1.6 fins/cm) while
high-capacity reheat coils have 144 fins/ft (4.7 fins/cm).
Hot Water or Steam
Face Area — ft
2
(cm
2
) 0.6 0.6 0.8 1.2 1.6 2.4 2.4
(557) (557) (743) (1120) (1490) (2230) (2230)
L x D x H — in. (cm) 15 x 1.5 x 6 15 x 1.5 x 6 20 x 1.5 x 6 29.5 x 1.5 x 6 38 x 1.5 x 6 57 x 1.5 x 6 57 x 1.5 x 6
(38 x 4 x 15) (38 x 4 x 15) (51 x 4 x 15) (75 x 4 x 15) (97 x 4 x 15) (145 x 4 x 15) (145 x 4 x 15)
Volume — gal (L) 0.12 (0.45) 0.12 (0.45) 0.15 (0.57) 0.22 (0.83) 0.28 (1.06) 0.42 (1.59) 0.42 (1.59)
Standard Capacity
(a)
Fins/ft (cm) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6)
High-Capacity
(a)
Fins/ft (cm) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
Fan/Motor Data
Fan Quantity 1112233
Size — Dia” x Width” (cm) 6.31 x 4 6.31 x 6.5 6.31 x 7.5 6.31 x 6.5 6.31 x 7.5 (1) 6.31 x 7.5 6.31 x 7.5
(16 x 10) (16 x 17) (16 x 19) (16 x 17) (16 x 19) (16 x 19) (16 x 19)
Size — Dia” x Width” (cm) (2) 6.31 x 6.5
(16 x 6.5)
Motor Quantity 1111122
Filter Data
1” (cm) TA and Pl. Media
Quantity 1111111
Size — in. (cm) 8-7/8 x 19-1/8 8-7/8 x 19-1/8 8-7/8 x 24-1/8 8-7/8 x 33-5/8 8-7/8 x 42-1/8 8-7/8 x 61-1/8 8-7/8 x 61-1/8
(23 x 49) (23 x 49) (23 x 61) (23 x 85) (23 x 107) (23 x 155) (23 x 155)
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity 1111111
Size — in. (cm) 5-1/2 x 19-1/8 5-1/2 x 19-1/8 5-1/2 x 24-1/8 5-1/2 x 33-5/8 5-/2 x 42-1/8 5-1/2 x 61-1/8 5-1/2 x 61-1/8
(14 x 49) (14 x 49) (14 x 61) (14 x 85) (14 x 107) (14 x 156) (14 x 156)

Table of Contents