Emergency Application
c
40 / 118
1.
2.
3.
4.
5.
6.
7.
5.11.2. Preventing the emergency units from switching on
The main power supply is switched on.
Ensure that emergency operation is not necessary.
Click on the "Main menu" symbol.
-> The "Main menu" is displayed
Click on the "Configuration" button
-> The "Configuration" page is displayed
Click on the "Emergency" tab
-> The "Emergency" tab is displayed
Click on the "Inhibit" button.
-> The LEDs of the emergency units emit a green double flash.
Switch off the main power supply within 15 minutes.
-> The emergency units do not switch on.
-> When the main power supply is switched on again, the emergency units are reactivated.
In order to reactivate the emergency units without switching the main power supply on and off again, click on
the "stop REST / INHIBIT" button.
...
I NOTICE
Not all emergency units support the "stop REST / INHIBIT" function.
I NOTICE
Not all emergency units support the "stop REST / INHIBIT" function.