EasyManua.ls Logo

Truma CP plus - Page 28

Truma CP plus
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
34020-01385 · 00 · 07/2022
EN
Troubleshooting guide Truma CP plus
Fault
code
Cause Remedy
E 122 H Lack of fuel due to low tank level, tank is empty and / or
vehicle is on a slope
Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar
system from on-board power supply)
Fill tank with fuel and then fill the fuel line (see operating instruc-
tions / initial start-up)
Make sure that the altitude kit is used for heating mode at altitudes
above 1500 m
If using the altitude kit, make sure that the correct metering pump
is selected
E 131 H No connection between heater and control panel Connect the heater and the control panel
E 132 H FrostControl heating element has a short circuit Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar sys-
tem from on-board power supply)
W 150 H Warm air temperature exceeded
Make sure that all warm air ducts are connected to the heater
Check whether the warm air ducts are damaged or kinked
Remove the blockage in the circulated air intake and ensure that
the installation space is sufficiently ventilated (see operating in-
structions/circulated air intake)
W 151 H Water temperature exceeded in heater mode
Switch heater off and allow to cool, fill water container with water
Make sure that all warm air ducts are connected to the heater
Check whether the warm air ducts are damaged or kinked
Remove the blockage in the circulated air intake and ensure that
the installation space is sufficiently ventilated (see operating in-
structions/circulated air intake)
E 152 H Water temperature exceeded in hot water mode Switch heater off and allow to cool, fill water container with water
W 160 H
W 161 H
12 V power supply faulty (low voltage)
Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar
system from on-board power supply)
Charge battery and check contacts, replace old battery
Short-term immediate action, switch off high-consumption ap-
pliances or start up vehicle engine until the heater starts running
(approx� 4 minutes)

Other manuals for Truma CP plus

Related product manuals