Troubleshooting guideTruma CP plus
Fault
code
Cause Remedy
E 162 H Window above cowl open (window switch) Close window above cowl
W 163 H One of the temperature switches has opened Allow the heater to cool� If this occurs frequently, contact
Truma Service
W 164 H 230 V power supply faulty
Check the 230 V power supply at the appliance input
Reset the 230 V overheating protection (see operating instructions)
Have an expert check the 230 V T10AH fuse and have it replaced
if necessary / Before opening the connection cover, completely
disconnect the appliance from the power supply / Replace the con-
nection cover before restarting the appliance
W 170 H Imminent low voltage < 11�5 V
Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar
system from on-board power supply)
Charge battery and check contacts, replace old battery
Short-term immediate action, switch off high-consumption ap-
pliances or start up vehicle engine until the heater starts running
(approx� 4 minutes)
W 255 H
No connection between heater and control panel
Heater has no 12 V power supply
Control panel cable faulty
Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar
system from on-board power supply)
Check the control panel cable and make sure there is connection
between the heater and the control panel
Have an expert check the device fuse and have it replaced if neces-
sary / Before opening the connection cover, completely disconnect
the device from the power supply / Replace the connection cover
before restarting the device
W 301 H,
W 417 H,
E 540 H
12 V power supply faulty (overvoltage) Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar sys-
tem from on-board power supply)
W 302 H,
W 418 H,
E 541 H
12 V power supply faulty (low voltage)
Ensure 12 V power supply under load at appliance input / check for
AC voltage components (disconnect power supply unit and solar
system from on-board power supply)
Charge battery and check contacts, replace old battery
Check function with motor running, check power supply unit or
other batteries

Other manuals for Truma CP plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Truma CP plus and is the answer not in the manual?

Truma CP plus Specifications

General IconGeneral
DisplayLCD
Power supply12 V DC
Quiescent current consumption (at 12 V)Approx. 5 mA
Temperature range-15 °C to +60 °C
Protection classIP20
CompatibilityTruma Combi heaters

Related product manuals