32
Part Two
Rm1 Setpnts Menu
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Room1 Heating
Supply Flow Rate
Heat Flow
The Heat Flow item sets the maximum supply flow for
heating.
0 to 10,000 CFM
NOTE
Heat Flow cannot
be set greater than
the Max Sup Flow
or less than the
Min Sup Flow
0 CFM
NOTE: Input7 must be configured to ROOM1 SUPPLY
AIR TEMP SENSOR for this item to be active.
Input3 must be configured to measure supply flow
for this item to be active.
The Cntrl Device item must be set to
SUPPLY/EXHAUST/TEMP for this item to be
active.
This item can be adjusted even if not active.
If Min Sup Flow is programmed to be higher than
Heat Flow or Cool Flow, Heat Flow or Cool
Flow will be reset to the Min Sup Flow setpoint.
Room1 Cooling
Flow Rate
Cool Flow
The Cool Flow item sets the maximum supply flow for
cooling.
0 to 10,000 CFM
NOTE
Cool Flow cannot
be set greater than
the Max Sup Flow
or less than the
Min Sup Flow
0 CFM
NOTE: Input3 must be configured to measure supply flow
for this item to be active.
The Cntrl Device item must be set to
SUPPLY/EXHAUST/TEMP for this item to be
active. This item can be adjusted even if not
active.
If Min Sup Flow is programmed to be higher than
Heat Flow or Cool Flow, Heat Flow or Cool
Flow will be reset to the Min Sup Flow setpoint.

Table of Contents

Other manuals for TSI Instruments PRESSURA RPC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments PRESSURA RPC30 and is the answer not in the manual?

TSI Instruments PRESSURA RPC30 Specifications

General IconGeneral
BrandTSI Instruments
ModelPRESSURA RPC30
CategoryController
LanguageEnglish

Related product manuals