EasyManua.ls Logo

turck FEN20-4IOL - Page 83

turck FEN20-4IOL
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V01.00 | 2019/12
83
Error code Designation acc. to
specification
Meaning
0x8021 SERV_NOTAVAIL_
LOCCTRL
Service temporarily not available, device is busy (e.
g. teaching or parameterization of the device at the
device active)
0x8022 SERV_NOTAVAIL_
DEVCTRL
Service temporarily not available, device is busy (e.
g. teaching or parameterization of the device via
DTM/PLC etc. active)
0x8023 IDX_NOT_WRITEABLE Access denied, Index cannot be written
0x8030 PAR_VALOUTOFRNG Parameter value out of the valid range
0x8031 PAR_VALGTLIM Parameter value value above the upper limit
0x8032 PAR_VALLTLIM Parameter value value below the lower limit
0x8033 VAL_LENOVRRUN Length of data to be written does not match the
length defined for this parameter
0x8034 VAL_LENUNDRUN
0x8035 FUNC_NOTAVAIL Function not available in the device
0x8036 FUNC_UNAVAILTEMP Function temporarily not available in the device
0x8040 PARA_SETINVALID Invalid parameter: Parameters not consistent with
other parameters in the device.
0x8041 PARA_SETINCONSIST Inconsistent parameters
0x8082 APP_DEVNOTRDY Application not ready, device busy
0x8100 UNSPECIFIC Vendor specific, according to device documenta-
tion
0x8101…
0x8FF
VENDOR_SPECIFIC
IO-Link Events Class (VSC 138)
Attr. no. Designation Get/Set Type Meaning
Dec. Hex.
1 0x01 IOL-Event 1 –
port
G USINT Port no. of the port which sends the
1st IO-Link Event.
16 0x10 IOL-Event 16 –
port
G USINT Port no. of the port which sends the
16th IO-Link Event.
17 0x11 IOL-Event 1 –
qualifier
G USINT Qualifier of the 1st IO-Link event
32 0x20 IOL-Event 16 –
qualifier
G USINT Qualifier of the 1st IO-Link event
33 0x21 IOL-Event 1–
Event Code
G USINT Event code of the 1st IO-Link event
48 0x30 IOL-Event 16–
Event Code
G USINT Event code of the 1st IO-Link event

Table of Contents

Related product manuals