Parameterizing and Configuring
Configuring the devices at EtherNet/IP
146
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Analog Output Class (VSC 132)
One instance is assigned to each channel:
n Instance 1: Channel 0
n Instance 2: Channel 1
n Instance 3: Channel 2
n Instance 4: Channel 3
Attribute no. Designation Get/Set Type Meaning
Dec. Hex.
1 0x01 Operation mode G/S USINT 0: voltage
1: Current
2 0x02 Current range G/S USINT 0: 0…20 mA
1: 4…20 mA
3 0x03 Voltage
range
G/S USINT 0: -10…+10 V
1: 0…10 V
2: 2…10 V
3: 0…5 V
4: 1…5 V
4 0x04 Data
representation
G/S USINT 0: Standard
1: NE43
2: Extended range
5 0x05 Deactivate
channel
G/S USINT 0 = no
1 = yes
6 0x06 Output recovery
mode
G/S USINT 0: automatic
1: manual
7 0x07 Deactivate
diagnostics
G/S USINT 0 = no
1 = yes
8 0x08 Output on field-
bus error
G USINT 0: default value
1: Substitute value
2: Current value
9 0x09 Substitute value G UINT Substitute value to be transferred
10 0x0A Overload G USINT 0: -
1: active
11 0x0B Wire break G USINT 0: -
1: active
12 0x0C output G UINT