9.3.2 Measurement value representation – TBEN-S2-4AO
Voltage – standard
Decimal hexadecimal
(two's complement)
-10…10 V
Dec. value = 3276.7 (1/V) × U
out
(V)
32767 7FFF Nominal range 10.0000 V
32766 7FFE 9.9997 V
16384 4000 5.0002 V
1 0001 0.000305 V
0 0000 0.00000 V
-1 FFFF -0.000305 V
-16384 C000 -5.0000 V
-32766 8001 -9.9997 V
-32767 8000 -10.0000 V
Decimal hexadecimal
(two's complement)
0…10 V
Dec. value = 3276.7 (1/V) × U
out
(V)
32767 7FFF Nominal range 10.0000 V
32766 7FFE 9.9997 V
16384 4000 5.0002 V
1 0001 0.000305 V
0 0000 0 V
-1 FFFF 0 V
-16384 C000 0 V
-32767 8001 0 V