Loading...
Operating
Evaluating diagnostic data
180
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
TBEN-S2-4AI – diagnostic data mapping
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Channel
0
n LLVU UFL OFL WBR V1AOL ULVE RTDSC CJE
Channel
1
n + 1 LLVU UFL OFL WBR V1AOL ULVE RTDSC CJE
Channel
2
n + 2 LLVU UFL OFL WBR V1AOL ULVE RTDSC CJE
Channel
3
n + 3 LLVU UFL OFL WBR V1AOL ULVE RTDSC CJE
PROFINET error codes
Station diagnostics (slot 0) PROFINET diagnostics
Diagnostics Error code Channel
Undervoltage
V1 0x0002 0
V2 0x0002 1
I/O diagnostics (slot 1) PROFINET diagnostics
Diagnostics Connector/pin Error code Channel
Wire break (WBR) C0…C3 0x0004 0…3
Overcurrent (RTD
only), (RTDSC)
0x0004
Overcurrent supply
VAUX1 (V1AOL)
0x0004
Upper limit value ex-
ceeded (ULVE)
0x0007
Overflow (OFL) 0x0007
Lower limit value un-
derrun (LLVU)
0x0008
Underflow (UFL) 0x0008
Cold junction error
(CJE)
0x0019

Table of Contents