Operating
Measurement value representation of analog modules
190
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Voltage – NE43
-10…10 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 10
-3
) V
> 11 V "Overload/Overcurrent" ON > 11000 > 2AF8
11.00 V 11000 2AF8
< 10.95 V "Overload/Overcurrent" OFF > 10950 < 2AC6
> 10.50 V "Upper limit value exceeded” ON > 10500 > 2904
< 10.25 V "Upper limit value exceeded" OFF > 10250 < 280A
10.00 V Nominal range 10000 2710
5.00 V 5000 1388
2.00 V 2000 07D0
0 V 0 0000
-2.00 V -2000 F830
-5.00 V -5000 EC78
-10.00 V -10000 D8F0
> -10.25 V "Lower limit value underrun" OFF > -10250 > D7F6
< -10.50 V "Lower limit value underrun" ON > -10500 < D6FC
> -10.95 V "Underflow" OFF > -10950 > D53A
-11.00 V -11000 D508
< -11.00 V "Underflow" ON > 11000 < D508
0…10 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 10
-3
) V
> 11 V "Overload/Overcurrent" ON > 11000 > 2AF8
11.00 V 11000 2AF8
< 10.95 V "Overload/Overcurrent" OFF > 10950 < 2AC6
> 10.50 V "Upper limit value exceeded” ON > 10500 > 2904
< 10.25 V "Upper limit value exceeded" OFF > 10250 < 280A
10.00 V Nominal range 10000 2710
5.00 V 5000 1388
2.00 V 2000 07D0
0 V 0 0000
> -0.03 V "Lower limit value underrun"
and "Underrun" OFF
> -30 > FFE2
< -0.05 V "Lower limit value underrun"
and "Underrun" ON
> -50 < FFCE