Operating
Measurement value representation of analog modules
192
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
1…5 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 10
-3
)/2 V
> 5.50 V "Overload/Overcurrent" ON > 11000 > 2AF8
5.50 V 11000 2AF8
< 5.45 V "Overload/Overcurrent" OFF > 10900 < 2A94
> 5.25 V "Upper limit value exceeded” ON > 10500 > 2904
< 5.13 V "Upper limit value exceeded" OFF > 10260 > 2814
5.00 V Nominal range 10000 2710
2.50 V 5000 1388
1.00 V 2000 07D0
> 0.95 V "Lower limit value underrun"
and "Underrun" OFF
> 1900 > 076B
< 0.90 V "Lower limit value underrun"
and "Underrun" ON
> 1800 > 0708
> 0.55 V "Wire break" OFF > 1100 > 044C
< 0.50 V "Wire break" ON > 1000 < 03E8
0 V 0 0000
> -0.03 V "Underflow" OFF > -60 > FFC4
< -0.05 V "Underflow" ON > -100 < FF9C
-1…1 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 10
-4
) V
> 1.100 V "Overload/Overcurrent" ON > 11000 > 2AF8
< 1.099 V "Overload/Overcurrent" OFF > 10990 < 2AEE
> 1.050 V "Upper limit value exceeded” ON > 10500 > 2904
< 1.052 V "Upper limit value exceeded" OFF > 10520 < 280A
1.000 V Nominal range 10000 2710
0.500 V 5000 1388
0 V 0 0000
- 0.500 V -5000 EC78
-1.000 V -10000 D8F0
> -1.025 V "Lower limit value underrun"
and "Underrun" OFF
> -10250 > D7F6
< -1.050 V "Lower limit value underrun"
and "Underrun" ON
> -10500 < D6FC
> -1.099 V "Underflow" OFF > -10990 > D512
< -1.100 V "Underflow" ON > -11000 < D508