Operating
Measurement value representation of analog modules
194
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
-50…50 mV Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 10
-5
)/2 V
> 0.0550 mV "Overload/Overcurrent" ON > 11000 > 2AF8
< 0.0549 mV "Overload/Overcurrent" OFF > 10990 < 2AE4
> 0.0525 mV "Upper limit value exceeded” ON > 10500 > 2904
< 0.0513 mV "Upper limit value exceeded" OFF > 10520 < 280A
0.0500 mV Nominal range 10000 2710
0.0250 mV 5000 1388
0 mV 0 0000
-0.0250 mV -5000 EC78
-0.0500 mV -10000 D8F0
> -0.0513 mV "Lower limit value underrun"
and "Underrun" OFF
> -10260 > D7F6
< -0.0525 mV "Lower limit value underrun"
and "Underrun" ON
> -10500 < D6FC
> -0.0549 mV "Underflow" OFF > -10980 > D51C
< -0.0550 mV "Underflow" ON > -11000 < D508
Current – standard
0…20 mA Diagnostics decimal hexadecimal
(two's complement)
Current value I
M
= (dec. value × 6.104 × 10
-4
) mA
> 20.20 mA "Upper limit value exceeded” ON 32767 7FFF
< 20.10 mA "Upper limit value exceeded" OFF 32767 7FFF
20 mA Nominal range 32767 7FFF
10.00 mA 16384 4000
0 mA 0 0000
> -0.10 mA "Lower limit value underrun"
and "Underrun" OFF
> -164 > FF5C
< -0.20 mA "Lower limit value underrun"
and "Underrun" ON
< -328 < FEB8