Parameterizing and Configuring
Configuring devices at Modbus TCP
88
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
TBEN-S2-8DXP – output registers
Meaning of the process output data [}53]
Register
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
OUT
0x0800 - - - - - - - - DX7
C3P2
DX6
C3P4
DX5
C2P2
DX4
C2P4
DX3
C2P2
DX2
C1P4
DX1
C0P2
DX0
C0P4
Latch reset
0x0801 - - - - - - - - DX7 DX6 DX5 DX4 DX3 DX2 DX1 DX0
CNT reset
0x0802 - - - - - - - - - - - - - - - CNT
reset
PWM Ch7
0x0803 - - - - - - - - Duty Cycle
PWM Ch7
0x0804 - - - - - - - - Duty Cycle
VAUX Control
0x0805 - - - - - - - - - - - - VAUX
1 P1
C3
VAUX
1 P1
C2
VAUX
1 P1
C1
VAUX
1 P1
C0