TVL 351
ISSUE 15
During the reset service the event code 299 “Limax3CP Reset Active” is logged, this can be silenced so the event
is not logged.
Limax3CP Constraints of use
Storage Temperature: -10 ºC to +60 ºC
Operating Temperature: 0 ºC to +40 ºC Note: The ambient temperature surrounding the
controller cabinet must be between 0 ºC and 40 ºC.
Humidity Operating Range: 0 - 90% relative humidity (non-condensing)
IP Rating: IP2X Protect against dust, moisture and water ingress.
Max operating life: 20 Years
Operation height: Up to 2000 m above sea level
The worst case reaction times of relay contacts OC, SR1 and SR2 when a safety function is triggered is
<55 ms and <45 ms for the eSGC.
Constraints for Installation of magnetic tape according to its instruction manual must be observed
A tape presence detector that trips on break of the magnetic tape must be installed.
Abbreviations.
CAN Controller area network
ETSL Emergency terminal speed limiting
OC Over-bridgeable contact
SGC Safety gear contact
SR1 Safety relay 1
UCM Unintended car movement