3
NOTE!
The controller must be unregistered in the
interface (if installed, Wave PLUS only) as
well. Go to menu Main menu > Preferences
> RF Link and unregister.
Caution!
Make sure the controller is in run mode.
For information about how to exit to run
mode, see section 10.4 Run mode > Exit to
run mode.
To unregister a system device:
1. Press and hold the OK button on the controller
until one of the channel LEDs starts flashing.
2. Use buttons < or > to move the pointer to the
power LED (LED flashes red).
3. Press the OK button to select system device
registration. The power LED starts flashing
according to the pattern long blink, short pause,
long blink. Channel 1 starts flashing red, or red/
green if a device is registered to that channel.
4. Use buttons < or > to move the pointer (LED
flashes red) to the selected channel (flashes green if
registered), see the following list.
1 = Touch screen interface (Wave PLUS only)
1 = Timer (Wave only)
2 = Relay module
3 = Public thermostat with outdoor sensor
4 = Public thermostat with heating/cooling switch
from contact or, in a Wave PLUS system only,
heating cooling switch from sensor input.
5 = Public thermostat with Comfort/ECO switch
5. Press the < and > buttons simultaneously for about
5 seconds until the LED for the selected channel
start flashing red.
10.7 Update controller software (Wave
PLUS only)
Software and update instructions can be found on the
Uponor website.
UK