04 Control mode
In this menu control mode for the thermostat is set.
If an external sensor is connected to the thermostat, a
control mode must be chosen to accommodate the extra
functionality of the sensor.
Current control mode is displayed (RT, RFT, RS or RO).
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to change control mode (see list
below).
RT = Room temperature
RFT = Room temperature with external floor sensor
RS = Remote sensor
RO = Room temperature with remote outdoor
sensor
3. Press OK to confirm the change and return to the
settings menu.
05 High floor temperature limitation
In this menu a limit on the maximum allowable floor
temperature is set.
This menu is only visible if control mode RFT is activated
in settings menu 04. For systems with an interface this
menu only shows the set value, changes are done in the
interface (Wave PLUS only).
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to change the parameter.
Default: 26 ˚C
Setting range: 20 – 35 ˚C, 0.5 ˚C increments
NOTE!
This parameter cannot be set lower than the
set value in settings menu 06 Low floor
temperature limitation.
3. Press OK to confirm the change and return to the
settings menu.
06 Low floor temperature limitation
In this menu a limit on the minimum allowable floor
temperature is set.
This menu is only visible if control mode RFT is activated
in settings menu 04. For systems with an interface this
menu only shows the set value, changes are done in the
interface (Wave PLUS only).
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to change the parameter.
Default: 20 ˚C
Setting range: 10 – 30 ˚C, 0.5 ˚C increments
NOTE!
If this parameter is set lower than 16 ˚C the
cooling icon will start flashing, warning for
risk of condensation in the system.
NOTE!
This parameter cannot be set higher than the
set value in settings menu 05 High floor
temperature limitation.
3. Press OK to confirm the change and return to the
settings menu.
07 Cooling allowed
In this menu it is set whether cooling is allowed in the
room or not.
This menu is not visible if an interface is connected
to the system. The settings are then available in the
interface (Wave PLUS only).
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to toggle between Yes and No.
Yes – shows the cooling demand icon
No – hides the cooling demand icon
3. Press OK to confirm the change and return to the
settings menu.
08 Display unit
In this menu temperature display unit is set.
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to toggle between Celsius and
Fahrenheit.
DEg ˚C – degrees Celsius
DEg ˚F – degrees Fahrenheit
3. Press OK to confirm the change and return to the
settings menu.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
64
UPONOR SMATRIX WAVE/WAVE PLUS · INSTALLATION AND OPERATION MANUAL