05 High floor temperature limitation
In this menu a limit on the maximum allowable floor
temperature is set. Limitations does not affect the
operation of the Move PLUS controller, when not
integrated to a Wave/Wave PLUS/Space/Space PLUS
controller.
This menu is only visible if control mode RFT is activated
in settings menu 04.
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to change the parameter.
Default: 26 ˚C
Setting range: 20 – 35 ˚C, 0.5 ˚C increments
NOTE!
This parameter cannot be set lower than the
set value in settings menu 06 Low floor
temperature limitation.
3. Press OK to confirm the change and return to the
settings menu.
06 Low floor temperature limitation
In this menu a limit on the minimum allowable floor
temperature is set. Limitations does not affect the
operation of the Move PLUS controller, when not
integrated to a Wave/Wave PLUS/Space/Space PLUS
controller.
This menu is only visible if control mode RFT is activated
in settings menu 04.
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to change the parameter.
Default: 20 ˚C
Setting range: 10 – 30 ˚C, 0.5 ˚C increments
NOTE!
If this parameter is set lower than 16 ˚C the
cooling icon will start flashing, warning for
risk of condensation in the system.
NOTE!
This parameter cannot be set higher than the
set value in settings menu 05 High floor
temperature limitation.
3. Press OK to confirm the change and return to the
settings menu.
07 Cooling allowed
In this menu it is set whether cooling is allowed in the
system or not.
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to toggle between Yes and No.
Yes – shows the cooling demand icon
No – hides the cooling demand icon
3. Press OK to confirm the change and return to the
settings menu.
08 Display unit
In this menu temperature display unit is set.
To change this setting:
1. Press OK and the parameter starts flashing.
2. Use buttons - or + to toggle between Celsius and
Fahrenheit.
DEg ˚C – degrees Celsius
DEg ˚F – degrees Fahrenheit
3. Press OK to confirm the change and return to the
settings menu.
09 Climatic controller integration
In this menu the thermostat is registered to the Move
PLUS controller.
Default value: no
To change this setting:
1. Press OK and the parameter starts flashing
2. Use buttons - or + to toggle between no, YEs and
CnF.
no – not integrated
YEs – Integrated (requires to be registered with the
Move controller first)
CnF – register with the Move PLUS controller,
confirm on the Move PLUS controller
3. Press OK to confirm the change and return to the
settings menu.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
65
UPONOR SMATRIX MOVE/MOVE PLUS
·
INSTALLATION AND OPERATION MANUAL

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor SmatrixMove and is the answer not in the manual?

Uponor SmatrixMove Specifications

General IconGeneral
BrandUponor
ModelSmatrixMove
CategoryTemperature Controller
LanguageEnglish

Related product manuals