USAutomatic SENTRY 300 S - Photo-eye or other safety accessory will not reverse the gate when closing or hold the gate open; Transmitter operating range seems short; Gate 1 or 2 opens and closes, but stop positions have changed; Gate 1 or Gate 2 only operates in one direction

USAutomatic SENTRY 300 S
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
10. Photo-eye or other
safety accessory will
not reverse the gate
when closing or hold
the gate open
1. Therstthingtocheckistheaccessorywiring.See
accessorywiringinformationonpage21.
2. AccessorybeingusedshouldbewiredwiththeN/Owire
connectedtoJ2pin5ontheSentrycontrolboard.
3. Verifythecontrolswitch“OperatingDirectionReverse”switch
issetinthecorrectposition,PulltoOpenswitchisOFF.
4. ConnectawiretoJ2.5thenstartthegateclosingandthen
touchthefreeendofthiswiretoJ2.2.Gateshouldstopand
reverse.Ifgatereversesthenthecontrolboardisworking
correctlyandtheaccessoryistheproblem.
5. Ifgatedoesnotstopandreverse,thecontrolboardisthe
problem.
11. Transmitter operating
range seems short
1. Replacethebatteriesinthetransmitter.
2. Verifythatthereceiverantenna(shortwireconnectedto
thereceiver)isnottwistedorrolledup.Itshouldbepointing
towardthecontrolboxcover.
3. Sometypeofradiofrequencyinterferenceisobstructing
signalfromtransmittertoreceiver.Possiblecausesare
electricfence,highvoltageelectriclinesingroundor
overhead.Radiotowersinthearea,militarybasesetc..In
somecasesthismightnotbeavoidedorpossiblyadifferent
frequencyreceiverneedstobeinstalled.
12. Gate 1 or 2 opens
and closes, but stop
positions have changed
1. Readjustretractorextendlimits
2. Verifygateopenorclosespeedisapproximately16seconds
3. Ifmuchslowerthan16seconds,seeproblem4.
13. Gate 1 or Gate 2
only operates in one
direction
1. Verifythatthecablefromlinearactuatortocontrolboardhas
notbeendamaged.
2. Ifcablehassplices,verifythatconnectionsaregoodandthat
anyexposedwiresaredry.
3. VerifythattheproblemexistsinboththeGate1andgate
2connectorsonthecontrolboard.makesuredipswitchfor
Gate1orgate2isONwhentesting.
4. Ifproblempersists,callSentryCustomerService.
1-866-711-0001.