Table 6: The options and their codes
Group Name Code
Approvals UL listed +GAUL
Not UL listed +GNUL
* = These options are not available for the NAM variation.
+ CAMH: MOTOR HEATER CONTROL
With this option, you can control the supply for the motor anti-condensation heater. The
external supply is connected to terminals -XD1.1 that are located in the lower part of the
cabinet. When the drive is not in Run state, the control relay +QAM changes the external
supply to the output terminals (-XDN). When the drive is in Run state, the control relay
disconnects the external supply to the motor heater. To disable the function, open the MCB –
FCN.
The control relay +QAM uses the GND (-XD2:13) and relay RO1 (-XD2:21) terminals.
The requirements: +CAPU Auxiliary AC supply terminals and +CAPD 24 VDC power supply
Fig. 17: The motor heater control
A. The heater element, not included in the
delivery
+CACH: CABINET HEATER
This option increases the inside temperature of the cabinet above the ambient temperature,
and thus prevents condensation in the cabinet. Each cabinet has 1 cabinet heater.
The external supply is connected to terminals -XD1.1. The heater element is of a self-
regulating type. When the drive is not in Run state, the control relay +QAM changes the
supply to the output terminals (-XD4). When the drive is in Run state, the control relay
disconnects the supply to the cabinet heater. To disable the function, open the MCB –FCE.
The control relay +QAM uses the GND (-XD2:13) and relay RO1 (-XD2:21) terminals.
The requirements: +CAPU Auxiliary AC supply terminals and +CAPD 24 VDC power supply
VACON · 36 MOUNTING
4