Fig. 32: The location of the fuses, MR12
A. The mains fuses B. The cabinet
The drive must be protected with fast acting aR-type fuses (-FC1) (see Table 10, Table 11,
Table 12 and Table 13). Do not use other fuses than these. These fuses are included in the
delivery.
The dimensions of the cables agree with the requirements of the standards EN 60204-1
and IEC 60364-5-52: 2001.
The cables are PVC-isolated.
The maximum ambient temperature is +30 °C.
The maximum temperature of the cable surface is +70 °C.
The maximum number of parallel cables on a ladder type tray is 9 side by side.
In other conditions, when you select the dimensions of the cables, refer to local safety
regulations, the input voltage and the load current of the drive.
VACON · 52 POWER CABLING