Table 8: The recommended cables and fuses in 380-500 V (IEC)
Enclosure
size
Type IL [A] Mains fuse
(gG/gL) [A]
Mains and motor
cable (Cu/AI) [mm2]
Mains and
motor cable
terminals,
bolt size
Grounding
terminal,
bolt size
MR8
0140 5 140 160
(3x70+35) (Cu)
(3x95+29) (Al)
M8 M8
0170 5 170 200
(3x95+50) (Cu)
(3x150+41) (Al)
M8 M8
0205 5 205 250
(3x120+70) (Cu)
(3x185+57) (Al)
M8 M8
MR9
0261 5 261 315
(3x185+95) (Cu)
2x(3x120+41) (Al)
M10 M8
0310 5 310 355
2x(3x95+50) (Cu)
2x(3x120+41) (Al)
M10 M8
MR10
0385 5 385 400
2x(3x120+70) (Cu)
2x(3x185+57) (Al)
M12 M8
0460 5 460 500
2x(3x150+70) (Cu)
2x(3x240+72) (Al)
M12 M8
0520 5 520 630
2x(3x185+95) (Cu)
3x(3x150+41) (Al)
M12 M8
0590 5 590 630
2x(3x240+120) (Cu)
3x(3x185+57) (Al)
M12 M8
MR12
0650 5 650 2 x 355
4x(3x95+50) (Cu)
4x(3x120+41) (Al)
M12 M8
0730 5 730 2 x 400
4x(3x95+50) (Cu)
4x(3x150+41) (Al)
M12 M8
0820 5 820 2 x 500
4x(3x120+70) (Cu)
4x(3x185+57) (Al)
M12 M8
0920 5 920 2 x 500
4x(3x150+70) (Cu)
4x(3x240+72) (Al)
M12 M8
1040 5 1040 2 x 630
4x(3x185+95) (Cu)
6x(3x150+41) (Al)
M12 M8
1180 5 1180 2 x 630
4x(3x240+120) (Cu)
6x(3x185+57) (Al)
M12 M8
POWER CABLING VACON · 53
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/