Table 9: The recommended cables and fuses in 525-690 V (IEC)
Enclosure
size
Type IL [A] Mains fuse
(gG/gL) [A]
Mains and motor
cable (Cu/AI) [mm2]
Mains and
motor cable
terminals,
bolt size
Grounding
terminal,
bolt size
MR8
0080 7 80 100
3x35+16 (Cu)
3x50+21 (Al)
M8 M8
0100 7 100 125
3x50+25 (Cu)
3x70+21 (Al)
M8 M8
0125 7 125 160
3x70+35 (Cu)
3x95+29 (Al)
M8 M8
MR9
0144 7 144 160
3x70+35 (Cu)
3x120+41 (Al)
M10 M8
0170 7 170 200
3x95+50 (Cu)
3x150+41 (Al)
M10 M8
0208 7 208 250
3x120+70 (Cu)
3x185+57 (Al)
M10 M8
MR10
0261 7 261 315
3x185+95 (Cu)
2x(3x95+29) (Al)
M12 M8
0325 7 325 355
3x240+120 (Cu)
2x(3x120+41) (Al)
M12 M8
0385 7 385 400
2x(3x120+70) (Cu)
2x(3x185+57) (Al)
M12 M8
0416 7 416 450
2x(3x120+70) (Cu)
2x(3x185+57) (Al)
M12 M8
MR12
0460 7 460 2 x 315
2x(3x150+70) (Cu)
2x(3x240+72) (Al)
M12 M8
0520 7 520 2 x 315
2x(3x185+95) (Cu)
4x(3x95+29) (Al)
M12 M8
0590 7 590 2 x 315
4x(3x70+35) (Cu)
4x(3x120+41) (Al)
M12 M8
0650 7 650 2 x 355
4x(3x95+50) (Cu)
4x(3x150+41) (Al)
M12 M8
0730 7 730 2 x 400
4x(3x120+70) (Cu)
4x(3x150+41) (Al)
M12 M8
0820 7 820 2 x 425
4x(3x120+70) (Cu)
4x(3x185+57) (Al)
M12 M8
VACON · 54 POWER CABLING
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/