NOTE!
The mains cable and fuse sizes are valid up to a cable length of 100 m, with mains
I
K
= 20 kA.
B
A
33 3
3
3
-F1
3
-FC1 -TA1-T1
Fig. 33: The location of the fuses, MR8-MR10
A. The mains fuses B. The cabinet
B
A
3
3 3
3
3
-F1
3
-FC1.1 -TA1.1
3
3
3
-F1
3
-FC1.2 -TA1.2
-T
Fig. 34: The location of the fuses, MR12
A. The mains fuses B. The cabinet
The cable dimensioning in Table 14 and Table 15 is in accordance with UL61800-5-1 and the
National Electric Code per table 310.15(B)(16). The values of the tables were calculated using
correction factors for a 40°C ambient operating temperature, and using AC drive cables with
a minimum insulation rating of 90°C. Refer to local or municipal regulations for more sizing
requirements.
The UL approval is valid for input voltage up to 600 V.
POWER CABLING VACON · 59