Table 14: The recommended cables and terminal lugs in 380-500 V (NAM)
Enclosure size Type I
L
(A) Mains and motor
cable (Cu) [AWG/
kcmil]
Mains and motor
cable
termination,
Panduit terminal
part number
Grounding
terminal, bolt and
lug size
MR8
0140 5 140 (3x2/0+3x10) LCAX2/0-38-X P10-56R-L
0170 5 170 (3x4/0+3x8) LCAX4/0-38-X LCAX8-56-L
0205 5 205 (3x262+3x6) LCAX250-38-X LCAX6-56-L
MR9
0261 5 261 2x(3x2/0+3x10) LCAX2/0-38-X P10-56R-L
0310 5 310 2x(3x4/0+3x8) LCAX4/0-38-X LCAX8-56-L
MR10
0385 5 385 2x(3x262+3x6) LCAX250-12-X LCAX6-56-L
0460 5 460 2x(3x313+3x6) LCAX300-12-6 LCAX6-56-L
0520 5 520 2x(3x373+3x6) LCAX350-12-6 LCAX6-56-L
0590 5 590 3x(3x262+3x6) LCAX250-12-X LCAX6-56-L
MR12
0650 5 650 4x(3x4/0+3x8) LCAX4/0-12-X LCAX8-56-L
0730 5 730 4x(3x4/0+3x8) LCAX4/0-12-X LCAX8-56-L
0820 5 820 4x(3x262+3x6) LCAX250-12-X LCAX6-56-L
0920 5 920 4x(3x313+3x6) LCAX300-12-6 LCAX6-56-L
1040 5 1040 4x(3x373+3x6) LCAX350-12-6 LCAX6-56-L
1180 5 1180 6x(3x262+3x6) LCAX250-12-X LCAX6-56-L
VACON · 60 POWER CABLING