Table 15: The recommended cables and terminal lugs in 525-690 V (NAM)
Enclosure size Type I
L
(A) Mains and motor
cable (Cu) [AWG/
kcmil]
Mains and motor
cable
termination,
Panduit terminal
part number
Grounding
terminal, bolt and
lug size
MR8
0080 7 80 (3x2+3x10) LCAX2-38-E P10-56R-L
0100 7 100 (3x1+3x10) LCAX1-38-X P10-56R-L
0125 7 125 (3x2/0+3x10) LCAX2/0-38-X P10-56R-L
MR9
0144 7 144 (3x4/0+3x8) LCAX4/0-38-X LCAX8-56-L
0170 7 170 (3x4/0+3x8) LCAX4/0-38-X LCAX8-56-L
0208 7 208 2x(3x1+3x10) LCAX1-38-X P10-56R-L
MR10
0261 7 261 2x(3x2/0+3x10) LCA2/0-12-X P10-56R-L
0325 7 325 2x(3x4/0+3x8) LCAX4/0-12-X LCAX8-56-L
0385 7 385 2x(3x262+3x6) LCAX250-12-X LCAX6-56-L
0416 7 416 2x(3x262+3x6) LCAX250-12-X LCAX6-56-L
MR12
0460 7 460 4x(3x1/0+3x10) LCAX1/0-12-X P10-56R-L
0520 7 520 4x(3x2/0+3x10) LCAX2/0-12-X P10-56R-L
0590 7 590 4x(3x4/0+3x8) LCAX4/0-12-X LCAX8-56-L
0650 7 650 4x(3x4/0+3x8) LCAX4/0-12-X LCAX8-56-L
0730 7 730 4x(3x4/0+3x8) LCAX4/0-12-X LCAX8-56-L
0820 7 820 4x(3x262+3x6) LCAX250-12-X LCAX6-56-L
POWER CABLING VACON · 61