3
vacon • 72 Descriptions of VACON® option boards
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
I/O terminals on OPTD1
NOTE: The terminals of the board are protected with a rubber pin. Be sure to leave the pin in the
unused terminals in order to avoid disturbances.
Connections between AC drives with OPTD1
Basic connection:
Connect the output 1 of Device 1 to the input 2 of Device 2 and the input of Device 1 to the output 2
of Device 2. Note that in the end devices one terminal pair remains unused. See Figure 24 below.
Table 39. OPTD1 I/O terminals
Terminal Technical information
1
H1
System Bus optical input 1 (RX1)
Use 1-mm optical cable (e.g. Agilent HFBR-RUS500 &
HFBR-4531/4532/ 4533 connectors)
2
H2
System Bus optical input 2 (RX2)
Use 1-mm optical cable (e.g. Agilent HFBR-RUS500 &
HFBR-4531/4532/4533 connectors)
3
H3
System Bus optical output 1 (TX1)
Use 1-mm optical cable (e.g. Agilent HFBR-RUS500)
4
H4
System Bus optical output 2 (TX2)
Use 1-mm optical cable (e.g. Agilent HFBR-RUS500)
Table 40.
Max.
number of devices in line
Max.
speed achieved [Mbit/s]
312
66
12 3
24 1.5