EasyManua.ls Logo

Vaisala HMP4 - Appendix A: Modbus Reference; Default Communication Settings; Function Codes; Data Encoding

Vaisala HMP4
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A. Modbus reference
A.1 Default communication settings
Table 72 Default Modbus serial communication settings
Property Description/Value
Serial bit rate 19200
Parity None
Number of data bits 8
Number of stop bits 2
Flow control None
Modbus device address 240
You can use up to ten probes on the same RS-485 line. You must configure each probe on the
line to have a dierent Modbus address.
A.2
 Function codes
Table 73 Modbus function codes
Function code
(decimal)
Function code
(hexadecimal)
Name Notes
03 03
hex
Read Holding
Registers
Class 0
16 10
hex
Write Multiple
Registers
Class 0
43 / 14 2B
hex
/ 0E
hex
Read Device
Identification
A.3 Data encoding
In the data registers, the numeric values are available in one or two formats with separate
register addresses: 32-bit IEEE floating point format and/or 16-bit signed integer format.
For values that have both 32-bit and 16-bit register available, use of the 32-bit
register is recommended. Some values may exceed the signed 16-bit range even
in normal operation.
Appendix A – Modbus reference
99

Table of Contents

Other manuals for Vaisala HMP4

Related product manuals