Display/keypad commands ___________________________________________________________
Vaisala _________________________________________________________________________ 35
Selecting the output quantities
HMT360 for Natural Gas
Two quantities are shown on the LCD. The upper half of the display
shows the moisture, whereas the lower half is reserved for the
temperature reading.
Upper half of the display
To modify the displayed quantity, turn the transmitter's CALIBRATION
ENABLED
/DISABLED dip switch to position ENABLED (up). Select the
required quantity with button on the display cover, and
acknowledge the value with button E. To complete the selections, turn
the dip switch back to position DISABLED (down).
When the OUTPUT QUANTITIES METRIC/NON METRIC dip switch is in the
METRIC (down) position, the available quantities are dew/frost point
temperature (Td °C), parts per million (ppm), and absolute humidity in
mg/m
3
(W). When the dip switch is in the NON METRIC (up) position,
the available quantities are dew/frost point temperature
(Td °F), parts per million (ppm), and absolute humidity in lb/mmscf
(W).
Lower half of the display
The OUTPUT QUANTITIES METRIC/NON METRIC dip switch can be used
to select between °C and °F.
It is possible to check the pressure setting of the transmitter by
pressing button . To return to the temperature reading, press button
again.
Selecting the analog outputs
You can select the output quantities for channels 1 and 2 by turning
the transmitter's CALIBRATION ENABLED/DISABLED dip switch to
position ENABLED (up) and the three OUTPUT SELECTION dip switches
to position
SPECIAL (all up).