USER'S GUIDE____________________________________________________________________
130 _________________________________________________________________ M211095EN-C
Parameter
Name
Default
Value
Allowed Values Units Description
cal_date Wind calibration date.
This is a read-only parameter.
com1_baud
com2_baud
4 0 = 300
1 = 1200
2 = 2400
3 = 4800
4 = 9600
5 = 19200
6 = 38400
7 = 57600
8 = 115200
Baud rates for serial ports COM1 and
COM2. Changes take effect only after
reset or the RESET command.
Note that a low bit rate can affect
measurement timing, if WMT700 cannot
send the data message before a new
measurement starts.
com1_data
com2_data
8 7 = 7 data bits
8 = 8 data bits
Data bits for serial ports COM1 and
COM2. Changes take effect only after
reset or the RESET command.
com1_delay
com2_delay
20 0 … 10000 ms COM1 and COM2 Response delay in
milliseconds.
com2_interf
0 0 = RS-485
1 = RS-422
2 = SDI-12
3 = RS-232
Interface for serial port COM2. (The
interface for serial port COM1 cannot be
changed.) Changes take effect only after
reset or the RESET command.
com1_parity
com2_parity
0 0 = none
1 = even
2 = odd
Parity for serial ports COM1 and COM2.
Changes take effect only after reset or
the RESET command.
com1_protocol
0 0 … 8 Protocol for serial port COM1.
0 = WMT700
1 = SDI-12
2 = WS425 F/G ASOS
3 = WS425 A/B ASCII
4 = WS425 A/B NMEA Standard
5 = WS425 A/B NMEA Extended
6= WS425 A/B WAT11
8 = MES12
com2_protocol 0 0 … 8 Protocol for serial port COM2.
0 = WMT700
1 = SDI-12
2 = WS425 F/G ASOS
3 = WS425 A/B ASCII
4 = WS425 A/B NMEA Standard
5 = WS425 A/B NMEA Extended
6= WS425 A/B WAT11
8 = MES12
com1_stop
com2_stop
1 1 = 1 bit
2 = 2 bits
Stop bits for serial ports COM1 and
COM2.
Changes take effect only after reset or
the RESET command.
heaterOn 1 0 = heater off
1 = automatic
Heater control. When the value is set to
1, WMT700 controls the heaters based
on the temperature and other conditions.
messages 1 0 = disabled
1 = enabled
Confirmation and error message
notifications.

Table of Contents