Technical description
3 Supporting functions
3.9 Combined overcurrent status
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
127
Parameter
Value
Unit
Description
Note
IncFltEvnt
On
Off
Disabling several start
and trip events of the
same fault
Several events are
enabled
*)
Several events of an
increasing fault is
disabled
**)
Set
ClrDly
0 ... 65535
s
Duration for active alarm
status AlrL1, Alr2, AlrL3
and OCs
Set
LINE FAULT
FltL1
FltL2
FltL3
0
1
Fault (=trip) status for
each phase.
0=No fault since fault
ClrDly
1=Fault is on
OCt
0
1
Combined overcurrent trip
status.
FltL1=FltL2=FltL3=0
FltL1=1 orFltL2=1 or
FltL3=1
LxTrip
On
Off
'On' Event enabling for
FltL1...3
Events are enabled
Events are disabled
Set
LxTripOff
On
Off
'Off' Event enabling for
FltL1...3
Events are enabled
Events are disabled
Set
OCTrip
On
Off
'On' Event enabling for
combined o/c trips
Events are enabled
Events are disabled
Set
OCTripOff
On
Off
'Off' Event enabling for
combined o/c starts
Events are enabled
Events are disabled
Set
IncFltEvnt
On
Off
Disabling several events
of the same fault
Several events are
enabled
*)
Several events of an
increasing fault is
disabled
**)
Set
ClrDly
0 ... 65535
s
Duration for active alarm
status FltL1, Flt2, FltL3
and OCt
Set