Technical description
9 Technical data
9.1 Connections
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
193
9.1.7. Remote control connection
Number of ports
1 option slot on rear panel
Electrical connection
RS 232
Glass fibre connection
Ethernet 10 Base-T
Protocols
ModBus TCP
DNP 3.0
IEC 61850
Ethernet IP
ANSI-85 (RS 232)
9.1.8. Analogue output connection (option)
Number of analogue mA output channels
1
Maximum output current
1 - 20 mA, step 1 mA
Minimum output current
0 - 19 mA, step 1 mA
Exception output current
0 20.50 mA, step 25 µA
Resolution
10 bit
Current step
< 25 µA
Accuracy
Class 1
Load resistance
RL < 600W