Technical description
5 Control functions
5.2 Digital inputs
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
143
Parameters of digital inputs
Parameter
Value
Unit
Description
Set
DI1,DI2
0
1
Status of digital input
DI COUNTERS
DI1, DI2
0 ... 65535
Cumulative active edge
counter
(Set)
DELAYS FOR DIGITAL INPUTS
DI1, DI2
0.00 ... 60.00
s
Definite delay for both on
and off transitions
Set
CONFIGURATION DI1 ... DI6
Inverted
no
yes
For normal open contacts
(NO). Active edge is 01
For normal closed
contacts (NC)
Active edge is 10
Set
Alarm display
no
yes
No pop-up display
Alarm pop-up display is
activated at active DI
edge
Set
On event
On
Off
Active edge event
enabled
Active edge event
disabled
Set
Off event
On
Off
Inactive edge event
enabled
Inactive edge event
disabled
Set
NAMES for DIGITAL INPUTS (editable with VAMPSET only)
Label
String of
max. 10
characters
Short name for DIs on
the local display
Default is "DIn", n=1...2
Set
Description
String of
max. 32
characters
Long name for DIs.
Default is
"Digital input n", n=1...2
Set
Set = An editable parameter (password needed)