25
Setup Vapor Recovery Setup
9.
Figure 35. Example Hose 1 Hose Map Locked
10.Continue with the next hose in numeric hose order, dispensing the appropriate amount of product, checking the
screen for information to populate, and then locking that hose.
Once the mapping process is complete, review your map.
Have all gasoline hoses been mapped?
Is the Hose ID and Hose FP Label correct?
Is Hose Label selection correct?
Is Air Flow Meter assignment correct?
Are the expected number of fuel meters assigned to a hose?
After completing hose mapping, ensure that all hoses are locked (see Figure 36).
Figure 36. Example Completed and Locked Meter Map
Hose Mapping - Manual Mode
Manual hose mapping can be used with the Hose Locked or Unlocked. To manually map or make an edit to a hose
map, knowledge of the FP (Logical) and the Meter (Fuel Meter) number is needed.
Example: After using Assist Mode to create the Hose Mapping Hose Map, it was discovered that Straight Grade
93 was skipped when mapping h 3: Blend3 (see Figure 37).