33
Setup Automatic Events: (Pump Mode = Pump Sense)
a. Via: Setup >Pumps and Lines > Lines:
i. Configure / Enable a Line
ii. Assign the appropriate gasoline Pump(s) to the Line
b. Via: Setup > Automatic Events > Device Tasks:
Add a task for required ISD Site Alarms
California Air Resources Board (CARB) requires that gasoline dispensing be shutdown for
specific ISD Site alarms and Hose alarms (See Table 3 on page 5).
i. Set the Device to the Gasoline Line
ii. Select each required ISD Site Alarm as a Trigger
iii. Hose Site Shutdown Option: Select the Hose Alarms for each Gasoline Hose as a Trigger
Figure 48. Example Device Task – Pump Sense (No Dispenser relay(s))
3. For each Relay setup in Step 1a above:
a. Via: Setup > Automatic Events > Device Tasks
:
Add a Task for LINE OUT alarm:
i. Set the Device to the Relay
ii. Select LINE OUT for the appropriate Line as a Trigger
Figure 49. Example Device Task – Pump Sense: Line Out (No Dispenser relay(s))
4. Dispenser Relay Shutdown option: For each Dispenser Relay:
a. Via: Setup > Devices > Relay
:
i. Configure/Enable Relay