Mag Probe Installation Probe Conduit Installation
25
Figure 17. Installing the Riser Adaptor
Probe Conduit Installation
Wiring Run Methods
IMPORTANT! The maximum probe-to-console cable length is 1000 feet (305m).
Legend for numbered boxes
1 Metal cap from kit
2 Adaptor ring from kit
3 Riser adaptor (Phil-Tite M/F4X4, or equivalent)
4Tank
WARNING
Probes operate in areas where flammable liquids and explosive vapors may be
present.
Improper installation may result in fire or explosion causing serious injury or
death.
1. Read thoroughly and follow the instructions in this manual and
those shipped with the probe.
2. Probe wiring conduit must not contain any other device’s wiring.
3. Probe wiring and conduits must enter the console only through
the designated intrinsically safe knockouts in the console (see
Figure 2).
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.