EasyManua.ls Logo

Vertiv Liebert DME22 - Page 97

Vertiv Liebert DME22
134 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | Liebert® DM | User Manual 88
Outdoor Fan Speed Controller (Only for 22 kW/27 kW)
When the current main menu is the active alarm value main menu identifier “A--”, press the ENT key to enter the active alarm
value menu interface. The switching operation process and sequence of active alarm value menu are shown in Figure 6-6.
Refer Table 8-2 for the conditions and troubleshooting of alarm generation.
Figure 6-6 Active Alarm Value Main Menu
Historical alarm value main menu interface
When the current main menu is the historical alarm value main menu identifier “H--”, press the ENT key to enter the
historical alarm value menu interface. The switching operation process and sequence of historical alarm value menu are
shown in Figure 6-7.
Figure 6-7 Historical Alarm Value Main Menu
A00: Input phase loss alarm
A01: SCR over temperature
A02: Fan 1 over temperture
A03: Fan 2 over temperture
A04: Pressure sensor failure
A05: EEPROM read failure
A06: SCR temperture sensor failure
A07: Frequency anomaly
0: Input phase loss alarm
1: SCR over temperature
2: Fan 1 over temperature
3: Fan 2 over temperature
4: Pressure sensor failure
5: EEPROM read failure
6: SCR temperture sensor failure
7: Frequency anomaly

Table of Contents

Related product manuals