Vertiv | Liebert® EDGE | Installer/User Guide 7
Chapter 2: INSTALLATION
2.1. What's Included
• USB cable; one 2 m long
• Quick Installation Guide
• Safety and Regulatory Guidelines
• Tower-support stands (2U and 3U models only)
• Rack-mount rail kit (except MT models)
2.2. Unpacking and Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local
dealer or your Vertiv representative immediately.
• Check the accessories included in packaging list. If there is any discrepancy, contact your local dealer or
your Vertiv representative immediately.
2.3. Preparation for Installation
2.3.1. Installation Environment
Unpack the UPS and conduct the following checks:
• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned O. The
installation environment should meet the specications listed in SPECIFICATIONS on page 41.
• Place it in an area of unrestricted air-ow around the unit, away from water, ammable liquids, gases,
corrosives, and conductive contaminants. Avoid direct sunlight.
• The socket outlet should be nearby and easily accessible.
• This UPS is not for use in a computer room as dened in the standard for the Protection of Electronic
Computer/Data Processing Equipment ANSI/NFPA 75.
NOTE: Operating the UPS in temperatures above 25°C reduces battery life.
2.3.2. Installation Clearances
Maintain at least 100 mm clearance in the front and rear. Do not obstruct the air inlets on the front panel and rear
panel. Blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the UPS.