Vertiv | Liebert® EDGE | Installer/User Guide 47
5.1. Battery Run Times
Table 5-4 Battery Run Time in Minutes, EDGE-500IRM1U
LOAD Internal Battery Only
% VA W
Minutes
100 500 450 5.2
90 450 405 6.3
80 400 360 7.6
75 375 337.5 8.4
70 350 315 9.3
60 300 270 11.7
50 250 225 15.0
40 200 180 20.1
30 150 135 28.9
25 125 112.5 32.2
20 100 90 42.7
10 50 45 88.7
Table 5-5 Battery Run Time in Minutes, EDGE-1000IRM1U
LOAD Internal Battery Only
% VA W
Minutes
100 1000 900 5.2
90 900 810 6.3
80 800 720 7.6
75 750 675 8.4
70 700 630 9.3
60 600 540 11.7
50 500 450 15.0
40 400 360 20.1
30 300 270 28.9
25 250 225 32.2
20 200 180 42.7
10 100 90 88.7