Vertiv | Liebert® EDGE | Installer/User Guide 51
Table 5-12 Battery Run Time in Minutes, EDGE-3000IRT2UXL/EDGE-3000IRT3UXL
LOAD
NUMBER OF EXTERNAL BATTERY CABINETS
Internal
Battery
Only
1 2 3 4 5 6
% VA W Minutes
100 3000 2700 6.1 19.8 39.9 61.5 83.7 106.2 129.0
90 2700 2430 7.2 23.1 46.1 70.5 95.5 120.9 146.4
80 2400 2160 8.6 27.4 53.9 81.9 110.4 139.2 168.2
75 2250 2025 9.4 29.9 58.6 88.6 119.2 150.0 181.1
70 2100 1890 10.3 33.0 64.1 96.5 129.5 162.7 196.1
60 1800 1620 12.8 40.8 78.1 116.6 155.6 194.8 234.2
50 1500 1350 16.2 51.9 97.5 144.3 191.5 238.9 286.4
40 1200 1080 21.4 68.6 126.6 185.6 244.9 304.4 364.0
30 900 810 30.6 96.9 175.1 254.2 333.5 413.0 492.6
25 750 675 33.6 106.2 191.0 276.5 362.3 448.3 534.3
20 600 540 43.8 137.1 243.4 350.4 457.6 564.9 672.3
10 300 270 93.7 284.1 491.2 698.7 906.4 1114.1 1321.9