Specications64
Table 7-1 UPS Specications, 5-kVA and 6-kVA models (Continued)
MODEL: GXT5-
5000IRT5UXLN* 5000IRT5UXLE 5000HVRT5UXLN* 6000IRT5UXLN* 6000IRT5UXLE
RATING
5000 VA/5000 W 6000 VA/6000 W
Environmental Parameters
Operating Temperature,
°C (°F)
0 to 40 (32 to 104) (no derating)
Storage Temperature, °C
(°F)
-15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA,at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Agency Parameters
Safety IEC62040-1:2008 version, GS mark
IEC62040-1:2008 version,
GS mark;
UL1778, c-UL listed
IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC
IEC/EN/AS 62040-2 2nd Ed
(Cat 2 – Table 6)
IEC/EN/AS 62040-2 2nd
Ed (Cat 2 – Table 6); FCC
Part 15 (Class A) CISPR22
Class A (RFI)
IEC/EN/AS 62040-2 2nd Ed
(Cat 2 – Table 6)
ESD
IEC/EN EN61000-4-2, Level 4,
Criteria A
IEC/EN EN61000-4-2,
Level 4, Criteria A
IEC/EN EN61000-4-2, Level 4,
Criteria A
Radiated Susceptibility
IEC/EN EN61000-4-3, Level 3,
Criteria A
IEC/EN EN61000-4-3,
Level 3, Criteria A
IEC/EN EN61000-4-3, Level 3,
Criteria A
Electrical Fast Transient
IEC/EN EN61000-4-4, Level 4,
Criteria A
IEC/EN EN61000-4-4,
Level 4, Criteria A
IEC/EN EN61000-4-4, Level 4,
Criteria A
Surge Immunity
IEC/EN EN61000-4-5, Level 4,
Criteria A
IEC/EN EN61000-4-5,
Level 4, Criteria A; ANSI
C62.41 Category B
IEC/EN EN61000-4-5, Level 4,
Criteria A
Transportation ISTA Procedure 1E
*Only these models are available in the ASIA PACIFIC region.