NOTICE
Condenser fans should be operated manually if they have not run for an extended time in an outdoor
environment. Before enabling the condenser for normal cooling operation fans should be run at full speed for at
least three hours once a month to move the bearings and allow any condensate that may have ingressed to
evaporate.
Condenser firmware release 1.06.045 & later include settings to operate condenser fans if they have been
inactive for more than 30 days.