Max Penalty—Decreases the time until the next maintenance cycle. A penalty should be used when a
service visit finds excessive wear on components.
Last Maintenance—Date set during the service call. It also indicates to other service personnel the date of
the last visit.
Service Engineer—Provides a label for the service representative to list either the company name or
representative’s name.
Confirm PM—Confirms that the service representative has completed the preventive maintenance and
resets the next maintenance date.
Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the last
preventive maintenance performed (Confirm PM), component starts, run hours and the penalty or bonus
set in the Liebert iCOM control.
Figure 6.20 Pump 1 settings, page 2 of 7
Number of Starts—Shows the number of starts for the unit’s Pump 1.
Run Hours—Shows the number of run hours for the unit’s Pump 1.
Average Run Time—Shows the average run time of the unit’s Pump 1.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will always take
the value from the worst component for the next maintenance indication.