NetSure
™
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
Retrieve Setting Param.run Procedure
See also “Backing Up the NCU Configuration” on page 29.
A file named “SettingParam.run” is automatically created/appended by the controller whenever a User (or the factory at the time of
shipment) makes changes to any parameter settings via the local display or Web Interface. This file contains changes made to alarm
setpoints and other settings such as float / equalize voltage, etc. This file can be saved to your computer so you can restore any custom
settings you may have made.
NOTE: It is strongly recommended that you save a copy of the SettingParam.run file whenever you customize any parameter settings.
Then, if you ever replace the controller or perform a "Restore Defaults" procedure, you can restore your customized settings by
downloading the previously saved SettingParam.run file back into the controller.
Prior to changing settings, ensure the current configuration package and "SettingParam.run" files are backed up. After making changes,
create new backup files.
Procedure
1. Click on the “Retrieve File” button to save the file named "SettingParam.run" to your computer. Select where you want the file
to be copied to on your computer.
NOTE: Ensure Internet Explorer security settings are set to enable a file to be copied to your computer.
To aid in file management, you may change the name of the “SettingParam.run” file to differentiate it from other "SettingParam.run"
files saved. The new name can use alpha and numeric characters preceding the original “SettingParam.run” name (the end of the
new file name must always be “SettingParam.run”; for example, an acceptable filename would be “seville4SettingParam.run”).
Figure 85. Retrieve SettingParam.run