Approved quality
CE designation according to current EC Directives
Qualitätsmarke der ÖVGW gemäß Gütezeichenverordnung
1942 DRGBl. I für Erzeugnisse des Gas- und Wasserfachs
Meets the requirements of the "Blue Angel" certificate of environmental
excellence to RAL UZ 39
1.2 Operating conditions
Requirements Implementation
1. Heating water flow rate none
2. Boiler return temperature
(minimum value)
35 ºC Installation of an efficient return tempera-
ture raising facility (e.g. through 4-way
mixer and minimum limit and/or return
temperature raising pump)
3. Low-end boiler water temperature
(also for frost protection)
35 ºC Through the Viessmann control unit
(standard delivery)