Manual VIPA System 300S SPEED7 Chapter 5 Deployment I/O periphery
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45 5-11
The counter values may be read by the output parameter COUNTVAL of
the SFB 47. There is also the possibility for direct access to the counter
values by means of the input address of the Count submodule.
There are the following possibilities for connection to the technological
functions:
24V incremental encoder, equipped with two tracks with 90° phase
offset
24V pulse generator with direction signal
24V proximity switch (e.g. BERO or light barrier)
For not all inputs are available at the same time, you may set the input
assignment for every counter via the parameterization. For each counter
the following inputs are available:
Channel
x
(A)
Pulse input for count signal res. track A of an encoder. Here you may
connect encoder with 1-, 2- or 4-tier evaluation.
Channel
x
(B)
Direction signal res. track B of the encoder. Via the parameterization you
may invert the direction signal.
Hardware gate
x
This input allows you to open the HW gate with a high peek and thus start
a count process. The usage of the HW gate may be parameterized.
Latch
x
With an edge 0-1 at Latch
x
the recent counter value is stored in a memory
that you may read at need.
Every counter has an assigned output channel. The following behavior for
the output channel may be set via parameterization:
No comparison: Output is not controlled and is switched in the same
way as a normal output.
Count value comparison value:
Output is set as long as counter value comparison value.
Count value comparison value:
Output is set as long as counter value comparison value.
Pulse at comparison value: You can specify a pulse period for
adaptation to the actuators you are using. The output is set for the given
pulse duration, as soon as the counter reached the comparison value. If
you have parameterized a main count direction the output is only set
when reaching the comparison value from the main counting direction.
The maximum pulse duration may amount to 510ms. By setting 0 as
pulse duration the output gets set as long as the comparison conditions
are fulfilled.
Read counter
Counter inputs
(Connections)
Counter outputs

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the VIPA System 300S SPEED7 CPU 313SC/DPM and is the answer not in the manual?

VIPA System 300S SPEED7 CPU 313SC/DPM Specifications

General IconGeneral
BrandVIPA
ModelSystem 300S SPEED7 CPU 313SC/DPM
CategoryControl Unit
LanguageEnglish

Related product manuals