Manual VIPA System 300V Chapter 6 Deployment CPU 31x with TCP/IP
HB130E - CPU - Rev. 11/50 6-15
Now the "parameter" window contains the basic initialization of your CP.
The following registers are supported:
The "parameter" window contains the following registers:
CP-Init (Basic initialization of the CP)
Firmware (Online firmware update)
Reboot (Start online reboot at the CP)
Password (Password for online engineering and firmware update)
IP-List (Access protection for IP addresses)
Clock-Init (Parameterization as time master)
Parameter-IP (System parameter for the IP protocol)
Syskonfig (Parameter for IPK)
The register "CP-Init" contains the basic initialization of your CP. Here you
parameterize addresses and other identification parameter of the CP.
Insert values for the following parameters under CP-Init and click on
[Apply]:
Station name, page frame basic address (0 fix), page frame amount (1 fix),
station address (000000000000 fix), IP address and subnet mask.
If needed, you get the IP address and the subnet mask from your system
operator, the rest of the settings remain unchanged.