Chapter 4 Deployment CPU 31x Manual VIPA System 300V
4-14 HB130E - CPU - Rev. 11/50
A maximum of 32 PG/OP connections is supported by MPI. The transfer
via MPI takes place with the following proceeding:
• Connect your PC to the MPI jack of your CPU via a MPI programming
cable.
• Load your project in the SIMATIC Manager from Siemens.
• Choose in the menu Options > Set PG/PC interface
• Select in the according list the "PC Adapter (MPI)"; if appropriate you
have to add it first, then click on [Properties].
• Set in the register MPI the transfer parameters of your MPI net and type
a valid
address.
• Switch to the register Local connection
• Set the COM port of the PCs and the transfer rate 38400Baud for the
MPI programming cable from VIPA.
• Via PLC > Load to module you may transfer your project via MPI to the
CPU and save it on a MMC via
PLC > Copy RAM to ROM if one is
plugged.
Transfer via Profibus is only available by DP master, if projected as master
and assigned with a Profibus address before. A maximum of 31 PG/OP
connections is supported by Profibus. The transfer via MPI takes place with
the following proceeding:
• Connect your PC to the MPI jack of your CPU via a MPI programming
cable.
• Load your project in the Siemens SIMATIC Manager.
• Choose in the menu Options > Set PG/PC interface
• Select in the according list the "PC Adapter (Profibus)"; if appropriate
you have to add it first, then click on [Properties].
• Set in the register Profibus the transfer parameters of your Profibus net
and type a valid
Profibus address. The Profibus address must be
assigned to the DP master by a project before.
• Switch to the register Local connection
• Set the COM port of the PCs and the transfer rate 38400Baud for the
MPI programming cable from VIPA.
• Via PLC > Load to module you may transfer your project via Profibus to
the CPU and save it on a MMC via
PLC > Copy RAM to ROM if one is
plugged.
Approach transfer
via MP
2
I
Approach transfer
via Profibus