SECTION 5: TROUBLESHOOTING GUIDE 80
EPI800 Manual.doc EPI 800 MANUAL 2001 Vision Microsystems Inc.
FUEL LEVEL PROBE TRANSDUCER TEST
1. Check that wires are correctly installed according to the harness
wiring instructions and have not broken, shorted or come loose.
2. The following measurements are made by first fabricating and
then inserting a ‘bare wire jumper’ between each respective
transducer lead to harness terminal (i.e. red to red, black to
black, white to white). If any test fails, stop and contact the
factory.
3. Measure continuity (ohms) of each wire from transducer
connector pin to appropriate harness connector pin. There should
be very low resistance if the wire is intact. If resistance is greater
that 0.7 ohms, then stop and correct connections.
4. Perform the following tests with instrument power ON.
Meter
Common
Meter
Plus
Desired
Value
Unit under test
BLK
RED
4.95 to 5.05 vdc
3010009/10/12/13
BLK
WHT
1.9 to 2.4 vdc
3010009/10/12/13
BLK
WHT
1.7 to 4.0 vac
3010009/10/12/13
Shut off power and disconnect probe from harness (or
harness from IO interface).
BLK
RED
8900 to 9200
3010009/10/12/13
BLK
WHT
14200 to 14700
3010009/10/12/13
WHT
RED
5300 to 5500
3010009/10/12/13