Operation
GPi 3200
/4300
4.16 Starting the Generator (S Models)
Starting
procedure
Troubleshooti
ng
CAUTION
Personal injury
or
machine damage hazards. Starting the generator with equipment
attached can damage the generator
or
the equipment. Unexpected equipment
start-up can cause personal injury.
IIJI>
Disconnect all equpment from the generator before starting it.
Follow the procedure below to start the machine.
1.
Turn the engine switch (h) to the CHOKE position (or the RUN position if the
engine is warm or the ambient temperature is high).
wc_gr006666
2. Insert the starting key into the key switch (g).
3. Turn the starting key clockwise to the "I" (ON) position, then farther to the
START position. The engine will start.
NOTICE:
To
avoid machine damage, do not engage the starter motor continuously
for more than five seconds.
If the engine fails to start, return the starting key to the
ON position, wait approximately 10 seconds, and then try again.
Do not turn the key switch
to
the START position when the engine is running.
4.
If
you started the engine with the engine switch in the CHOKE position, allow the
engine to run for
20-30
seconds and then turn the engine switch to the RUN
position.
5.
Use the LED changeover switch (n) to switch to display voltage on the LCD. A
reading
of
120V indicates that the generator is operating properly.
• If the engine does not start after several attempts, repeat the starting procedure
with the engine switch turned to the RUN position.
• Try starting the machine manually. See Starting the Generator (Manual Start
Models).
•
If
the engine still does not start, refer to the Troubleshooting chapter.
W4CKER
NEUSON
38
wc_tx001875gb.fm