Section 3
Auto-Zone CV & CV-EX
3-6 Programming
Full System Access
Full Access Menu
Set Time & Date
The System Manager has its own built in Real Time Clock. It broadcasts this time once a
day, at midnight, to synchronize all the other units on your Auto-Zone system. Although
the times are displayed on the Main Screen in a standard 12-hour format, they are
programmed using the 24-hour Military format. Once the time has been entered, it is also
broadcast immediately to all other units on the system. That means that you only need to
program the System Manager time to set the Real Time Clocks for all units on your
communications loop.
Programming Time
1) Set Time & Date
2) Read/Reset Units
3) New Passcodes
4) Rebuild Alarm Map
If you selected the MENU key from the first menu screen you
can gain full system access. However, you must be a Level 2
user. If you haven't already been asked to enter the passcode,
you will be asked before the Full Access Menu is displayed.
This prevents the casual user from being overwhelmed with the
full amount of data and setpoints available to the Level 2 user.
Program Time/Date
Day (Sunday=0): 1
Enter Hr. (0-23): 9
Enter Minutes : 53
Day
- Enter the Day of the Week (0 to 6) with
Sunday = 0
Hours (Hr)
- Enter Hours in 24-Hour Military Format
(1700 = 5:00 PM)
Minutes
- Enter the Minutes (0 to 59)